Glass Bulp Sprinkler Head
Dry Pendent Type
Dry Sprinklers are thermo sensitive glass bulp spry sprinklers which are suitable for freezing areas. When firing,
the heat-sensitive liquid in the bulp expands, and breaks the glass, it makes the plugger to open the waterway.
Specification
Model No. |
SWP-D1 |
SWP-D2 |
Fusing Point |
68°C |
93°C |
Ceiling Temp |
39°C |
56°C |
Glass Bulp Color |
Red |
Green |
R T I |
Standard Response Type |
Spray Form |
Pendent Type |
Connect Thread |
PT 1" (25A) |
Orifice Dia. |
Ø 13 |
Design Flow |
80 LPM (1kg/cm² - 1min) |
Material |
Forged Brass |
Finishing |
Ni-Cr plate |
Indicating items
FRAME |
SWM |
DEFLECTOR |
Manufacturing year, SSU, Operating temperature, SWM |
GLASS BULP |
DI 937K |
Assembly drawing